A Magnetic Level Gage may be an excellent addition to the drum level instrumentation on your Power Boiler application. However, in order to properly apply a Magnetic Level Gage on a Power Boiler, you must first understand the specific minimum requirements for water level instrumentation in the ASME Boiler and Pressure Vessel Code. A functional water gage glass is
required on all boilers and it must be in service at all times on applications operating up to 400 PSIG (3 MPa). For boilers operated at greater pressures, the Code permits the minimum use of two remote (indirect reading) level indicators on continuous display for the operator combined with a water gage glass. The use of a magnetic type level indicator has a Code limit of 900 PSI
(6 MPa). Furthermore, when two remote indicators are in service, the gage glass may be isolated, but must be kept in good working condition.
Gage glasses are often used to confirm the actual water level in the drum and for comparison with other instruments, especially at start-up. In most modern boiler installations, the operator is located in the control area, in which the gage glass is not within their line of site. To address this situation, the Code requires two independent level indicators that are maintained on continuous
display for the operator. Therefore, the Code requirement for two remote indicators provides this critical level information to the operator with validation and confidence. In addition, we recommend using multiple technologies for remote indicators to prevent the risk of common mode failure between systems. The most common technologies of remote water level indication instruments used on Section 1 Power Boilers are those listed below:
• Conductivity probe
• Differential Pressure
• Guided Wave Radar
• Magnetic Level Sensing

Magnetic Level Gages are comprised of a stainless steel chamber with an internal float containing a magnet that causes the externally mounted indicator to respond to changes with the water level in the boiler. Since the operator is not able to physically see the water as compared to a gage glass, this device is defined as a remote (indirect) level indicator, even though it is locally mounted near the drum. This instrument may be equipped with a transmitter to detect, transmit, and display the level information for the operator in the control area. Any water level sensing device that is externally mounted and relies on conductivity, signal detection & transmission, or magnetic sensing technology is considered to be a remote (indirect) type level indicator. A gage glass is the only type of direct reading level indicator.
Successful installations require attention to detail. When specifying and installing a Magnetic Level gage on a Power Boiler application, the ASME Boiler Code requirements are very specific
with respect to the position limits of the indication scale relative to the vessel connections. The indication range must meet the same requirements as a gage glass. These ASME Section 1 Code requirements are significantly different when compared to the vast majority of Magnetic Level Gages installed on applications other than Power Boilers.
The following Code rules must be met to apply a Magnetic Level Gage:
1. The maximum operating pressure is 900 PSIG (6 MPa). This eliminates the concern for deviations with level accuracy on frequent cycling applications at higher pressure service.
2. The indication scale limitations are between 2 inches above the danger point, as determined by the boiler manufacturer and the low side of the outside diameter of the steam connection exiting the drum.
3. The attachment of any external switches or transmitters to a Magnetic Level Gage for control functions is prohibited.
4. The use of a Magnetic Level Gage does not replace the Code required gage glass.
5. A Magnetic Level Gage may NOT be used to function as a water column. Other accessories such as a gage glass are prohibited from being attached.
6. Magnetic Level Gages must be installed with isolation and drain valves.
7. Refer to Subsections PG-12 and PG-60 in Section 1 of the Code for additional details.

To maximize accurate and dependable service life, periodic (annual) float inspections are recommended in order to remove any potential debris that may collect on it. This reasonable maintenance inspection along with periodic blow downs of the sensing lines will ensure continued and reliable indication. The quality of the boiler water in an application will guide the user with the frequency of inspection. Applications with quality water treatment will require less maintenance.

Help
RAVEBO gebruikt cookies om deze website gebruiksvriendelijker te maken. Deze cookies hebben uitsluitend functionele, communicatieve of analytische doeleinden. Door gebruik te maken van deze website gaat u akkoord met het gebruik van cookies. Voor meer informatie zie ons Cookie Statement.
Ok Weigeren
Selecteer een afdeling:*
Selecteer een afdeling.

Vul een naam in:*
Vul een naam in

Telefoonnummer:
Invalid Input

E-mailadres:*
Invalid Input

Onderwerp:*
Geef u bericht een onderwerp.

Bericht:*
Voer een bericht in.

Security*
Security
RefreshInvalid Input